Does anyone know if MW electrical code requires metal or PVC conduit when running romex from a junction box to an electrical receptacle in a basement? Or is it ok to just run the romex tapered to the wall to the receptacle from the junction box with its own shielding? Thanks |
   
wharfrat
Citizen Username: Wharfrat
Post Number: 988 Registered: 6-2001
| Posted on Saturday, February 28, 2004 - 10:36 am: |    |
The National Electical Code says conduit. Play it safe since it's going to be exposed. With offset fittings, couplings and pull elbows it not difficult to install conduit. |
   
bobk
Citizen Username: Bobk
Post Number: 4825 Registered: 5-2001
| Posted on Saturday, February 28, 2004 - 11:47 am: |    |
This has got to be the most violated part of the electrical code, at least here in MW.
|
   
NRL
Citizen Username: Nrl
Post Number: 481 Registered: 8-2003
| Posted on Saturday, February 28, 2004 - 1:31 pm: |    |
Conduit it is! Thanks folks! |